Power factor: Lagging and Leading

<< Click to Display Table of Contents >>

Navigation:  Project design > Grid-connected system definition > Power Factor >

Power factor: Lagging and Leading

Previous pageReturn to chapter overviewNext page

In an AC circuit, the current is ideally in phase with the voltage. But inductive or capacitive devices will produce a phase shift named phi ([-90° ... +90°) , described by "cos(phi)" or "Power Factor",

Many confusions may arise with the sign of this Phase shift. For a consumer device, we have 2 situations:

Lagging:

-Phi > 0
-The current lags (follows) the voltage  
-This is produced by inductive devices  (motors, transformers, etc)
-This produces what is named "Lagging reactive power", expressed in [kVAr]

Leading:

-Phi < 0
-The current is ahead of the voltage  
-This is produced by capacitive devices,
-This produces what is named "Leading reactive power", expressed in [kVAr]

Inverter output

Now the output circuits of the inverters have the possibility of electronically creating a Phase shift (generating reactive power) at "no energy cost", i.e. without consuming any additional Active Power,  

Therefore the Grid managers may require from the PV plants to "consume" Reactive power, for compensating the Lagging Reactive power produced by the numerous motors on the grid.

In this case on the output diagram, the denomination of the reactive energy is labelled "Reactive energy absorbed from the grid" when the required Cos(phi) is negative (Leading).